Detailed Specifications:
Feature | Description |
---|---|
Function | The OSYSU is used to monitor the open position of an OS&Y (outside screw and yoke) type gate valve |
Models Available | Two models are available: OSYSU-1 with one set of SPDT (Form C) contacts and OSYSU-2 with two sets of contacts |
Valve Compatibility | Compatible with OS&Y valves ranging in size from 2″ to 12″ (50mm to 300mm) |
Installation Requirements | Ensure the groove in the valve stem is at least as wide as the OSYSU roller or trip rod and at least 1/2″ deep. If not, use a 3/8″ round file on the groove |
Listings and Approvals | UL Listed & FM Approved |